| 2016-06-23 17:41:16 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: |
| | A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7 |
| | COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE |
| | PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL |
| | DRAWINGS SHOWING THE TILE THAT WAS APPROVED. |
| | RESPONSE: SECTION 4.2.2 OF ESR-1775 REPORT SUBMITTED |
| | REQUIRES WIND UPLIFT RESISTANCE DESIGN FOR BASIC WIND |
| | SPEEDS ABOVE 100MPH. PROVIDE DESIGN CRITERIA. DESIGNER |
| | OF RECORD TO SPECIFY ROOF TILE FASTENING METHOD AS |
| | REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| | SPECIFYING SCREWS, THEN SPECIFY TYPE AND NUMBER OF |
| | SCREWS. IF SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT |
| | APPROVAL FOR THE ROOF TILE ADHESIVE. |
| | B) ROOF TILE ADHESIVE IF SPECIFIED BY THE DESIGNER OF |
| | RECORD. |
| | C) INSWING FRENCH DOORS AS SHOWN ON PLANS. |
| | RESPONSE: NOA 15-0409.03 SUBMITTED IS FOR "OUTSWING" |
| | DOORS. NEED PRODUCT APPROVAL FOR "INSWING" DOORS AS |
| | SHOWN ON PLANS. |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK |
| | MULLION SIZE TO BE USED TO VERIFY COMPLIANCE WITH |
| | CALCULATED DESIGN PRESSURES. |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL |
| | FRAMING PLANS AND DETAILS. MISSING SOME CONNECTOR'S |
| | PRODUCT APPROVALS. |
| | F) ALL PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | 2- ENGINEER OF RECORD TO REVIEW/APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS. |
| | |