| 2016-03-31 19:15:16 | JOB PERMIT NUMBER: 16031390 |
| | JOB ADDRESS: 2163 REGENTS CIRCLE |
| | WEST PALM BEACH FLORIDA |
| | DATE: MARCH 31 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - SITE CURRENT APPLICABLE CODE STANDARD NEC 2011 |
| | - PROVIDE INTERSYSTEM BONDING TERMINAL AND SHOW WATER |
| | BEING BONDED TO GROUNDING ELECTRODE ON RISER DIAGRAM |
| | NEC 250 |
| | - PANEL ? S ? REFLECTS AN INCORRECT BREAKER SIZE ON |
| | PANEL SCHEDULE ? A ? AS A 20 AMP ? FURTHERMORE PROVIDE |
| | OVERCURRENT PROTECTION SIZES ON PANEL SCHEDULE ? A ? |
| | FOR AC UNITS , WATER HEATER , DRYER AND RANGE. |
| | - BALCONIES REQUIRE A GFCI RECEPTACLE OUTSIDE PER NEC |
| | 210.52 E 3 |
| | - STAIRWAY LIGHTING MUST BE ON A 3 WAY SWITCH PER NEC |
| | 210.70 2 C |
| | - ATTIC ENTRANCE MUST HAVE A LIGHT PER NEC 210.70 3 AND |
| | MAKE SURE PROPER WORKING CLEARANCE FOR ATTIC AC IS |
| | PROVIDED. |
| | |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |
| | 516-805-6713 |