Plan Review Notes
Plan Review Notes For Permit 16031390
Permit Number 16031390
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-28 15:37:28RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET S2:
 A) ACCORDING TO SEC. R301.2.1.4.3 OF FBC-RESIDENTIAL,
 5TH EDITION (2014), THIS BUILDING IS LOCATED IN
 EXPOSURE "C" NOT "B". REVISE THE DESIGN LOADING PER FBC
 2014 INFORMATION AND THE DESIGN CRITERIA. ALSO REVISE
 THE COMPONENTS AND CLADDING WIND PRESSURES ACCORDINGLY.
  
 B) DESIGN CRITERIA:
 (1) ROOF MATERIAL IS CONCRETE TILES NOT SHINGLES.
 REVISE AS REQUIRED. SEE PRODUCT APPROVAL SUBMITTED.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 (2) CLARIFY WHY THE FLOOR DEAD LOAD IS 10PSF SHINGLES?.
 SEC. R301.A FBC-RESIDENTIAL.
  
 (3) REVISE ROOF PITCH TO MATCH ELEVATIONS ON SHEET A2.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 C) REVISE THE WIND ZONE WIDTH "A" OF THE DESIGN LOADING
 PER FBC 2014. ACCORDING TO NOTE OF FIGURE R301.2(7)
 FBC-RESIDENTIAL THE WIDTH OF "A" IS 4 FEET IN ALL
 CASES. REVISE AS REQUIRED.
  
 D) PROVIDE COMPLETE AND CLEAR DETAIL SHOWING
 CONSTRUCTION OF NEW CONCRETE PAD FOR THE NEW STEEL
 COLUMN. DETAIL #5 DOESN'T MATCH INFORMATION SHOWN ON
 THE EXISTING FOOTING LOCATION FLOOR PLAN ON SHEET S1.
 IT IS NOT CLEAR HOW THE NEW CONCRETE PAD IS GOING TO BE
 CONSTRUCTED WHERE THERE IS AND EXISTING FOOTING. THERE
 ARE NO SPECS HOW TO DEAL WITH THE EXISTING CONCRETE
 BLOCK WALL FOOTING. SEC. R301.1 FBC-RESIDENTIAL.
  
 E) PARTIAL EXTERIOR WALL SECTION IS SHOWN INCORRECTLY.
 THE FLOOR TRUSSES ARE REPRESENTED AS STEEL BAR JOISTS
 NOT FLOOR TRUSSES. THIS IS MISLEADING THE TYPE OF
 CONSTRUCTION. REVISE AS REQUIRED TO REPRESENT WOOD
 FLOOR TRUSSES.. SEC. 107.2.1 CITY AMENDMENTS.
  
 F) WHERE IS DETAIL #4 TAKEN AT?. PROVIDE COMPLETE
 SPECIFICATIONS FOR THE PLATE SUPPORTING THE W14 X 43
 STEEL BEAM. PROVIDE COMPLETE INFORMATION SHOWING HOW IS
 THE CONCRETE BLOCK BLOCK SUPPORTED BY THIS BEAM. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 G) WHERE IS DETAIL #3 TAKEN AT?. CLARIFY WHY SPECIFYING
 SIMPSON CCCQ-SDS 2.5 FOR ONLY ONE BEAM TO POST
 CONNECTION. SEE PICTURE OF SPECIFIED CONNECTOR. ALSO,
 CLARIFY WHY ANCHORING WOOD POST BASE WITH TWIST STRAP.
 PROVIDE ENGINEERING ANALYSIS SHOWING HOW THE LATERAL
 LOADS ARE RESISTED. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH CONNECTOR SCHEDULE ON SHEET S1.
  
 H) PROVIDE COMPLETE SPECIFICATIONS FOR NEW CONCRETE
 BEAM SPECIFIED ON DETAILS #2, AND #7. SEC. R301.1
 FBC-RESIDENTIAL.
  
 3- SHEET S1:
 A) PROVIDE COMPLETE BEAM AND LINTEL SCHEDULE THAT
 REFLECTS BEAMS/LINTELS SHOWN ON THE SECOND AND ROOF
 FRAMING PLANS. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) CLEARLY SPECIFY THE CONNECTORS AT THE ENDS OF ALL
 BEAMS. SEC. R301.1 FBC-RESIDENTIAL.
  
 C) REVISE CONNECTORS SPECIFIED FOR THE ROOF TRUSSES
 ABOVE THE NEW BALCONY. CONNECTOR SPECIFIED IS FOR
 MASONRY CONSTRUCTION NOT FOR WOOD BEAMS. REVISE AS
 REQUIRED. SEC. R301.1 FBC-RESIDENTIAL.
  
 D) CLEARLY SPECIFY TOP AND BOTTOM CONNECTORS FOR THE
 NEW BALCONY WOOD POSTS. COORDINATE WITH DETAIL #3 ON
 SHEET S2. SEC. R301.1 FBC-RESIDENTIAL.
  
 E) CLARIFY CONNECTOR U3 SPECIFIED ON THE CONNECTOR
 SCHEDULE. WHY USING THIS TYPE OF HANGER FOR A PRECAST
 LINTEL. SEE NOTE U3 BELOW THE CONNECTOR SCHEDULE AND
 LEGEND FOR RB1 ON SAME SHEET. SEC. R301.1
 FBC-RESIDENTIAL.
  
 F) ROOF PLAN NOTES: CLARIFY WHY THE LIVE LOAD TOP CHORD
 ON NOTE #11 OF ROOF PLAN NOTES IS "20PSF REDUCIBLE".
 ALSO, COORDINATE ALL LOADS WITH THE DESIGN CRITERIA ON
 SHEET S2. COORDINATE WITH ITEM # 2(C) ABOVE. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 4- SHEET D-1: UPDATE GENERAL NOTE #1 THE CURRENT CODE
 IS 2014 NOT 2010. CHAPTER 553 F.S.
  
 5- SHEET A-1: UPDATE GENERAL NOTE #8 THE CURRENT CODE
 IS 2014 NOT 2001. CHAPTER 553 F.S.
  
 6- SHEET A-3:
 A) UPDATE GENERAL NOTE #8 THE CURRENT CODE IS 2014 NOT
 2001. CHAPTER 553 F.S.
  
 B) THE ROOF SLOPE SHOWN ON THE ROOF FRAMING PLAN
 DOESN'T MATCH ROOF SLOPE SHOWN ON THE EXTERIOR
 ELEVATIONS. REVISE AS REQUIRED TO MATCH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 7- SPECIFY CARBON MONOXIDE ALARMS WITHIN 10 FEET OF ALL
 BEDROOMS (INCLUDING 1ST FLOOR) AS REQUIRED BY SEC. R315
 FBC-RESIDENTIAL.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CEILING CONSTRUCTION ABOVE GARAGE TO SHOW COMPLIANCE
 WITH TABLE R302.6 FBC-RESIDENTIAL.
  
 9- VALUATION DECLARED IN-THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $37,448. THE PERMIT FEE BALANCE IS $843.33.
  
 10- PLANS TO BE COORDINATED WITH THE ENERGY
 CALCULATIONS. SPECIFY THE CEILINGS, FLOORS AND WALLS
 R-VALUE SPECIFIED ON THE ENERGY CALCULATIONS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 BALCONY GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE
 LOADS OF TABLE R301.5 FBC-RESIDENTIAL.
  
 12- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY AT BOTTOM OF FORM AS REQUIRED
 BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM
 INCLUDING BUILDER NAME, PERMIT OFFICE AND JURISDICTION
 NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). NOTE: THE JURISDICTION IS NOT PALM
 BEACH COUNTY.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES)AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF TILES. ONLY FLORIDA PRODUCT APPROVAL FL3505-R7
 COVER PAGE WAS SUBMITTED. NEED TO PROVIDE COMPLETE
 PRODUCT APPROVAL INFORMATION INCLUDING THE TECHNICAL
 DRAWINGS SHOWING THE TILE THAT WAS APPROVED.
  
 B) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) INSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO BE USED TO VERIFY COMPLIANCE WITH
 CALCULATED DESIGN PRESSURES.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL
 FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR. OR DESIGNER OF RECORD TO LIST THE
 CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 F) ALL PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  