| Date |
Text |
| 2016-05-03 08:04:47 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16031331 | | | 5/3/16 | | | | | | 1) THE EXHAUST DISCHARGE FROM THE MIXING BOOTHS SHALL | | | BE 30' FROM THE PROPERTY LINES PER SECTION 501.3.1 | | | FBC-14 MECHANICAL. PLEASE CORRECT THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|