| Notes |
| Date |
Text |
| 2016-03-31 09:04:30 | 1ST REVIEW: FBC 2014 MECHANICAL | | | REVISION #16031331 | | | MASTER #15041010 | | | 3/31/16 | | | | | | 1) CLARIFY HOW MAKE-UP AIR IS BEING PROVIDED FOR THE | | | MIXING BOOTH EXHAUST SYSTEMS, AND SHOW CALCULATIONS. | | | 2) PROVIDE CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN | | | FOR THE EXHAUST OUTLETS TO PROPERTY LINES, OPERABLE | | | OPENINGS INTO THE BUILDING , FROM GRADE, AND FROM | | | COMBUSTIBLE BUILDING ELEMENTS - SEE SECTION 501.3.1(1) | | | FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|