2016-03-31 08:30:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVISO- SHOW CLEARANCE FOR AC DISCONNECT. NEC
 110.26
 2. NOTE AT THE KITCHEN TO COMPLY WITH REQUIRED SPACING
 REQUIREMENTS OF FBC RES E3901.2.4
 3. VERIFY WATER MAIN IS BONDED AT SERVICE PER FBC RES
 E3606
 4. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  