| Plan Review Notes For Permit 16031311 |
| Permit Number |
16031311 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-31 08:30:31 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PROVISO- SHOW CLEARANCE FOR AC DISCONNECT. NEC | | | 110.26 | | | 2. NOTE AT THE KITCHEN TO COMPLY WITH REQUIRED SPACING | | | REQUIREMENTS OF FBC RES E3901.2.4 | | | 3. VERIFY WATER MAIN IS BONDED AT SERVICE PER FBC RES | | | E3606 | | | 4. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|