| Plan Review Notes For Permit 16031309 |
| Permit Number |
16031309 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-05-06 07:35:37 | 2ND ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PROVISO- SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE | | | AND FIRE ALARM FOR ROLL UP SHUTTER. FBC 107.3.5 | | | 2. AS-BUILT TO REFLECT WHAT BRANCH CIRCUITS WHERE USED | | | FOR THE NEW POWER RECEPTACLES. FBC 107.3.5 | | | 3. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|