| 2016-03-31 15:09:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. SHEET A 1.0 - THE PROPOSED PROJECT SHALL MEET THE |
| | REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE |
| | PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 |
| | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR |
| | STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | |
| | 2. SHEET A 1.0 - THE NATURE OF THE REMODEL REQUIRES AN |
| | EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR |
| | CODE COVERAGE AND COMPLIANCE. ANY REMOVAL AND/OR |
| | CONSTRUCTION OF WALLS REQUIRE AN EVALUATION. |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | 3. SHEET A 1.0 - TWO NEW DOORS ARE INDICATED ON THE |
| | REMODLED FIRE WALL. THE SUBMITTED PALNS DO NOT INDICATE |
| | A DOOR OR HARDWARE SCHEDULE. THE NEW DOOR AND HARDWARE |
| | SET SHALL COMPLY WITH THE REQUIRMENTS EQUAL TO THE FIRE |
| | RATING OF THE WALL ASSEMBLY. |
| | |
| | 4. SHEET A 2.0 - THERE ARE NO EXITS SIGNS INDICATED. |
| | PLEASE PROVIDE EXIT SIGNS ACCORDING TO THE LIFE SAFETY |
| | PLAN. |
| | |
| | 5. SHEET A 2.0 - THERE IS A DIMENSION OF 1' 9" BETWEEN |
| | OFFICE FURNITURE/EQUIPMENT THAT ISOF INSUFFICIENT WIDTH |
| | FOR EXIT PATH EGRESS. PLEASE PROVIDE A MINIMUM |
| | COMPLIANT WIDTH OF 36" PER NFPA 101, CHAPTER 7, MEANS |
| | OF EGRESS. |
| | |
| | 6. SHEET A 2.0 - THE 1-HOUR WALL DRAWING DOES NOT HAVE |
| | A U.L. LISTING NUMBER REFERENCE. PLEASE PROVIDE THE |
| | LISTING NUMBER. |
| | |
| | PETER LEDUC |