| 2016-03-31 07:41:30 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PROVISO- SEPARATE PERMITS REQUIRED FOR LOW VOLTAGE | | | AND FIRE ALARM FOR ROLL UP SHUTTER. FBC 107.3.5 | | | 2. PROVIDE ONE EXTRA SHEET OF A-1.0 FOR STAMPS AND | | | RECORD. A-2.0 SUBMITTED INADVERTENTLY ON SECOND SET | | | 3. AS-BUILT TO REFLECT WHAT BRANCH CIRCUITS WHERE USED | | | FOR THE NEW POWER RECEPTACLES. FBC 107.3.5 | | | 4. GENERAL NOTES TO MAINTAIN FIRE RATING AROUND FIRE | | | RATED WALLS. NEC 300.21 | | | 5. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|