| Plan Review Notes For Permit 16031307 |
| Permit Number |
16031307 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-28 17:49:10 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - RISER DIAGRAM SHOWS NO DISCONNECTING MEANS OF THE | | | ELECTRICAL SERVICE PLEASE LOCATE NEAREST POINT OF | | | ENTRY. NEC 230.70 A1 | | | KEEP IN MIND ALL DISCONNECTS MUST BE GROUPED AND | | | PROPERLY LABELED. NEC 230.72 A , NEC 408.4 B | | | | | | - GROUNDING DETAIL TO INCLUDE INTERSYSTEM BONDING | | | TERMINAL. NEC 250.94 | | | | | | - CLARIFY IF METER ENCLOSURE LUGS ARE RATED FOR DUAL | | | WIRES ? ( ACCORDING TO DRAWING ) |
|