| Date |
Text |
| 2016-04-04 18:05:52 | TRUSS PACKAGE REVIEW COMMENTS. |
| | FBC-5TH EDITION (2014). |
| | |
| | 1- THE TRUSS DRAWINGS NEED TO BE REVIEWED AND APPROVED |
| | BY THE ENGINEER OF RECORD AS REQUIRED BY F.A.C. SEC. |
| | 61G15-31.003. THE ENGINEER OF RECORD IS FARID ABUGATTAS |
| | NOT AFFINITY ARCHITECTS. PACKAGE WAS REVIEWED BY THE |
| | ARCHITECT NOT THE ENGINEER. REVISE AS REQUIRED. |
| | |
| | 2- ALL DRAWINGS AND DOCUMENTS NEED THE ENGINEER'S |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE. RUBBER STAMP IS NOT ALLOWED. |
| | |
| | 3- THE TRUSS INDEX SHEET DOESN'T COMPLY WITH FAC SEC. |
| | 61G15-31.003. MISSING THE ENGINEER OF RECORD |
| | INFORMATION. |
| | |
| | 4- THE INDIVIDUAL TRUSSES ARE DESIGNED BASED ON |
| | EXPOSURE "C". THIS BUILDING IS LOCATED IN EXPOSURE "D". |
| | REVISE ALL TRUSS DRAWINGS AS REQUIRED. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 5- GENERAL STANDARD ENGINEERING PAGES SUBMITTED: |
| | A) NEED ORIGINAL SEAL AND SIGNATURE ON EACH DRAWING AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | B) UPDATE ALL DRAWINGS TO THE CURRENT BUILDING CODE. |
| | CHAPTER 553 FLORIDA STATUTE. |
| | |
| | C) UPDATE ALL DRAWINGS TO THE CORRECT BUILDING EXPOSURE |
| | AND THAT APPLIES TO THIS JOB. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | D) SOME DRAWINGS ARE REFERENCING OLD ASCE EDITIONS AND |
| | THE MILES PER OUR DON'T CORRESPOND TO THE ACTUAL |
| | BUILDING. UPDATE AS REQUIRED. SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | NOTE: PROVIDE ONLY THE DETAILS THAT APPLY TO THIS JOB |
| | TO AVOID CONFLICTS/DELAYS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |