| Notes |
| Date |
Text |
| 2016-03-29 16:22:01 | (1) FIRE ALARM INSTALLATION SHALL COMPLY WITH NEC, NFPA | | | 70 AND 72. ALL FIRE PROTECTION EQUIPMENT SHALL REMAIN | | | INSERVICE DURING ALL PHASES OF CONSTRUCTION AND | | | INSTALLATION. | | | | | | (2) NFPA 90A-6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN | | | AIR DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: | | | DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY BRANCH | | | CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A CAPACITY | | | GREATER THAN 944 L/SEC (2000 FT3/MIN) AT EACH STORY | | | PRIOR TO THE CONNECTION TO A COMMON RETURN AND PRIOR TO | | | ANY RECIRCULATION OR FRESH AIR INLET CONNECTION IN AIR | | | RETURN SYSTEMS HAVING A CAPACITY GREATER THAN 7080 | | | L/SEC (15,000 FT3/MIN) AND SERVING MORE THAN ONE STORY. | | | | | | (3) NFPA 72-10.18.2.4, 2010 VERIFICATION OF COMPLIANT | | | INSTALLATION. WHERE REQUIRED, COMPLIANCE OF THE | | | COMPLETED INSTALLATION WITH THE REQUIREMENTS OF THIS | | | CODE, AS IMPLEMENTED VIA THE REFERRING CODE(S), | | | SPECIFICATIONS, AND/OR OTHER CRITERIA APPLICABLE TO THE | | | SPECIFIC INSTALLATION, SHALL BE CERTIFIED BY A | | | QUALIFIED AND IMPARTIAL THIRD-PARTY ORGANIZATION | | | ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. | | | | | | FRANK STALLWORTH, FIRE INSPECTOR I | | | WEST PALM BEACH FIRE PREVENTION BUREAU | | | 500 N. DIXIE HWY | | | WEST PALM BEACH, FLORIDA 33401 | | | OFFFICE: 561-840-4780 | | | FAX: 561-840-4774 | | | [email protected] | | | | | | |
|