Plan Review Notes
Plan Review Notes For Permit 16031268
Permit Number 16031268
Review Stop G
Sequence Number 1
Notes
Date Text
2016-03-30 06:37:141) INDICATE TYPE OF VENT MATERIAL FOR THE VENTS.
 2) SUBMIT A COPY OF THE INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATER.FBC 107.2.1.
 3) SHOW THE HEIGHT OF THE VENTS ABOVE THE FINISH GRADE.
 COMPLY WITH THE INSTALLATION MANUAL.
 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE NEW WATER
 HEATERS PER 2014 FUEL GAS CODE SEC.304.1.
 5) SUBMIT A GAS RISER DIAGRAM FOR CHANGES BEING MADE TO
 THE GAS PIPING. FBC 107.1.SHOW THE TOTAL DEVELOPED
 LENGTH FROM THE SOURCE OF DELIVERY ( METER) TO THE MOST
 REMOTE OUTLET.
 7) INDICATE ON THE PLANS THE TYPE OF GAS PIPE BEING
 INSTALLED.FBC 107.2.1.
 8) INDICATE ON THE PLANS THE PSI OF THE GAS SYSTEM.2014
 FGC SEC.402.2.
 9) A SEPARATE PERMIT IS REQUIRED FOR ELECTRIC.
  