| Plan Review Notes For Permit 16031253 |
| Permit Number |
16031253 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-28 11:37:18 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC-5TH EDITION (2014). | | | | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR THE FLAT ROOF TO BE INSTALLED. | | | | | | 2- FROM FLAT ROOF PRODUCT APPROVAL REQUIRED BY ITEM #1 | | | ABOVE: | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION | | | (2014). | | | | | | B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES REQUIRED BY R301, THEN SIGNED AND SEALED RAS | | | 117 WILL BE REQUIRED. SEE LIMITATIONS ON PRODUCT | | | APPROVAL SUBMITTED. | | | | | | 3- NOTICE OF COMMENCEMENT REQUIRED. SEC. 713 FL. ST. | | | | | | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED | | | TO $7,060. THE PERMIT FEE BALANCE IS $248.13. | | | | | | 5- SPECIFY THE SHINGLES ROOF PITCH. SEC. R905.2.2 OF | | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|