| 2016-03-30 16:22:41 | ELECTRICAL REVIEW COMMENTS |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | 1. 1. REGARDLESS OF WHEN THE CONVERSION WAS COMPLETED, |
| | IT IS BEING PERMITTED NOW AND THEREFORE SHALL COMPLY |
| | WITH CURRENT NATIONAL ELECTRICAL CODE REQUIREMENTS. |
| | (2011). |
| | 2. IN ADDITION TO THE EXISTING OUTLETS INDICATED ON THE |
| | DRAWING, YOU SHALL ADD THOSE MARKED IN RED TO COMPLY |
| | WITH MINIMUM CODE REQUIREMENTS. MARKINGS ARE |
| | APPROXIMATE, CONSULT WITH INSPECTOR IN THE FIELD FOR |
| | ACCURATE REQUIREMENTS. |
| | 3. OF THE NEW REQUIRED OUTLETS MARKED ON THE PLANS, |
| | THOSE HIGHLIGHTED IN YELLOW SHALL BE GFCI PROTECTED FOR |
| | THE KITCHEN COUNTERS AND BATHROOMS. |
| | 4. THOSE OUTLETS HIGHLIGHTED IN GREEN SHALL BE IN |
| | ADDITION TO GFCI PROTECTED, BE WEATHER RESISTANT AND |
| | HAVE AN IN-USE TYPE COVER AS WELL. |
| | 5. BATHROOM TO APT 1 REQUIRES AN EXHAUST FAN WHICH |
| | SHOULD COME ON WITH THE LIGHTS. |
| | 6. APT. 2 IS MISSING A WALL SWITCH ADJACENT TO THE MAIN |
| | ENTRY FOR THE CEILING LIGHT. |
| | 7. NEC 406.12 ALL RECEPTACLES IN A DWELLING SHALL BE |
| | TAMPER RESISTANT. |
| | 8. NEC 210.12, ARC-FAULT REQUIREMENTS AS PER NEC SHALL |
| | BE COMPLIED WITH. |
| | 9. NEC 240.24(B) REQUIRES THAT EACH TENANT HAVE ACCESS |
| | TO THEIR PANEL AT ALL TIMES. THEREFORE, UNLESS EACH |
| | TENANT HAS THEIR PANEL INSIDE THEIR UNIT AND YOU HAVE A |
| | COMMON ELECTRICAL PANEL FOR BOTH UNITS, THE PANEL SHALL |
| | BE IN A PLACE ACCESSIBLE TO BOTH TENANTS. |
| | 10. NEC 408.4 YOU SHALL SUBMIT LOAD CALCS AND A PANEL |
| | SCHEDULE |
| | 11. NEC 215.5 YOU SHALL PROVIDE A RISER DIAGRAM SHOWING |
| | CONDUCTOR SIZING AND INDICATE NUMBER AND LOCATION OF |
| | EVERY PANEL. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |