2016-05-09 06:51:261) THE FRONT SHEET OF THE PLANS STATE" 90%
 CONSSTRUCTION DOCUMENT-NOT FOR CONSTRUCTION". CLARIFY.
 2) INDICATE THE CURRENT OCCUPANCY TYPE OF THE BUILDING
 AND THE PROPOSED OCCUPANCY TYPE OF THE BUILDING ON THE
 PLANS PER FBC SEC. 302.
 3) SANITARY FACILITIES ARE REQUIRED PER THE 2014 FP
 SEC. 403 & TABLE 403.1 OR THEY SHALL BE AVAILABLE
 WITHIN A PATH OF TRAVEL NOT TOO EXCEED 500 FEET.FPC
 SEC. 403.3.3.
 4) HOT OR TEMPERED WATER SHALL BE SUPPLIED FOR BATHING
 OR WASHING PURPOSES PER FPC SEC.607.1.
 5) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 REQUIRED SANITARY FACILITIES.FBC 107.3.5.1.3.
 6) SANITARY FACILITIES SHALL COMPLY WITH FLA.
 ACCESSIBILITY CODE.
  