| Plan Review Notes For Permit 16031240 |
| Permit Number |
16031240 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-09 06:51:26 | 1) THE FRONT SHEET OF THE PLANS STATE" 90% | | | CONSSTRUCTION DOCUMENT-NOT FOR CONSTRUCTION". CLARIFY. | | | 2) INDICATE THE CURRENT OCCUPANCY TYPE OF THE BUILDING | | | AND THE PROPOSED OCCUPANCY TYPE OF THE BUILDING ON THE | | | PLANS PER FBC SEC. 302. | | | 3) SANITARY FACILITIES ARE REQUIRED PER THE 2014 FP | | | SEC. 403 & TABLE 403.1 OR THEY SHALL BE AVAILABLE | | | WITHIN A PATH OF TRAVEL NOT TOO EXCEED 500 FEET.FPC | | | SEC. 403.3.3. | | | 4) HOT OR TEMPERED WATER SHALL BE SUPPLIED FOR BATHING | | | OR WASHING PURPOSES PER FPC SEC.607.1. | | | 5) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | | REQUIRED SANITARY FACILITIES.FBC 107.3.5.1.3. | | | 6) SANITARY FACILITIES SHALL COMPLY WITH FLA. | | | ACCESSIBILITY CODE. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|