Plan Review Notes
Plan Review Notes For Permit 16031240
Permit Number 16031240
Review Stop M
Sequence Number 1
Notes
Date Text
2016-05-06 09:34:011ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16031240
 5/6/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS PER TABLE
 403.3 AND INDICATE HOW OUTDOOR AIR WILL BE SUPPLIED TO
 THE NEW OCCUPANCY.
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 3) PROVIDE WIND LOAD TIE-DOWN ENGINEERING FOR
 CONSTRUCTION OF THE CONDENSER PAD AND MOUNTING THE
 CONDENSER TO THE PAD- SECTION 301.15 FBC-14 MECHANICAL.
  