| 2016-05-06 09:34:01 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16031240 | | | 5/6/16 | | | | | | 1) PROVIDE MINIMUM VENTILATION CALCULATIONS PER TABLE | | | 403.3 AND INDICATE HOW OUTDOOR AIR WILL BE SUPPLIED TO | | | THE NEW OCCUPANCY. | | | 2) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. | | | 3) PROVIDE WIND LOAD TIE-DOWN ENGINEERING FOR | | | CONSTRUCTION OF THE CONDENSER PAD AND MOUNTING THE | | | CONDENSER TO THE PAD- SECTION 301.15 FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|