| Plan Review Notes For Permit 16031240 |
| Permit Number |
16031240 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-05-06 09:09:42 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE | | | PERMIT FOR ALL LOW VOLTAGE SYSTEM, ACCESS CONTROL, | | | SECURITY, ETC. | | | 2. CLARIFY THE FEEDER CONDUCTORS SHOWN FOR PANEL A @#3 | | | FOR A 110A. #3 CONDUCTOR GOOD FOR UP TO 100A PER TABLE | | | NEC 310.15B16 | | | 3. A MCB IS REQUIRED FOR PANEL A, BUT IT IS SHOWN AS A | | | MLO PANEL. SEE NEC 408.36B CLARIFY | | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE | | | FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | | REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|