2016-05-06 09:09:42APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE
 PERMIT FOR ALL LOW VOLTAGE SYSTEM, ACCESS CONTROL,
 SECURITY, ETC.
 2. CLARIFY THE FEEDER CONDUCTORS SHOWN FOR PANEL A @#3
 FOR A 110A. #3 CONDUCTOR GOOD FOR UP TO 100A PER TABLE
 NEC 310.15B16
 3. A MCB IS REQUIRED FOR PANEL A, BUT IT IS SHOWN AS A
 MLO PANEL. SEE NEC 408.36B CLARIFY
 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  