| 2016-05-05 15:46:47 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16031240 |
| | ADD: 1009 BANYAN BLVD. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: NO CONTACT INFORMATION |
| | E-MAIL: NO CONTACT INFORMATION |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 05/2016 |
| | ACTION: DENIED |
| | |
| | 1) VALUE FOR THE MOVING OF THIS STRUCTURE, FOUNDATION |
| | AND THE REBUILDING OF THE INTERIOR SPACE (MEP), NEW |
| | ROOF LUDOWICI HIP/ RIDGE TERMINAL BALLS, NEW WINDOWS |
| | AND DOORS WILL BE MORE THAN STATED IN THE PERMIT VALUE. |
| | |
| | PERMIT FEES/ PLAN REVIEW: |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) NO ASBESTOS REPORT WAS SUBMITTED. ASBESTOS: IN |
| | ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO ADVISE |
| | YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY TO |
| | COMPLY WITH THE STATE & FEDERAL ASBESTOS REGULATIONS, |
| | INCLUDING SECTION 376.60 F. S. AND CFR 61- NESHAP |
| | REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS SURVEYS |
| | AND SUBMISSION OF WRITTEN NOTIFICATION TO THE |
| | DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: * |
| | DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 355-3070 |
| | |
| | 3) HISTORIC BUILDINGS. 1206.1 INVESTIGATION AND |
| | EVALUATION REPORT. AN HISTORIC BUILDING UNDERGOING |
| | ALTERATION OR CHANGE OF OCCUPANCY SHALL BE INVESTIGATED |
| | AND EVALUATED. IF IT IS INTENDED THAT THE BUILDING MEET |
| | THE REQUIREMENTS OF THIS CHAPTER, A WRITTEN REPORT |
| | SHALL BE PREPARED AND FILED WITH THE BUILDING OFFICIAL |
| | BY A FLORIDA-REGISTERED ARCHITECT OR ENGINEER. SUCH |
| | REPORT SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF |
| | SECTIONS 4.3.1.2 THROUGH 4.3.2 OF NFPA 914, CODE FOR |
| | FIRE PROTECTION OF HISTORIC STRUCTURES AND SHALL |
| | IDENTIFY EACH REQUIRED SAFETY FEATURE THAT IS IN |
| | COMPLIANCE WITH THIS CHAPTER AND WHERE COMPLIANCE WITH |
| | THIS OR OTHER CHAPTERS WOULD BE DAMAGING TO THE |
| | CONTRIBUTING HISTORIC FEATURES. IN ADDITION, THE REPORT |
| | SHALL DESCRIBE EACH FEATURE THAT IS NOT IN COMPLIANCE |
| | AND DEMONSTRATE HOW THE INTENT OF THE PROVISIONS OF |
| | THIS OR OTHER CHAPTERS ARE COMPLIED WITH IN PROVIDING |
| | AN EQUIVALENT LEVEL OF SAFETY. PLEASE SUPPLY TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 4) SHEET S-0: |
| | 4A) FOUNDATION NOTE #1 EXCAVATION AND SOILS RELATED |
| | WORK SHALL BE PERFORMED IN ACCORDANCE WITH A |
| | GEOTECHNICAL REPORT. PLEASE REVIEW THE 2014 FBC-B |
| | SECTION 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 4B) SHEET S-0 THE DESIGN LOADING FOR THIS STRUCTURE: |
| | |
| | 4C) INDICATES THIS TO BE A CBS BUILDING, WHEREAS THE |
| | BUILDING TO BE MOVED IS A WOOD FRAME STRUCTURE, SHEET |
| | S-1 WALL SECTION ONLY SHOWS 2 COURSES OF BLOCK WITH A |
| | BOND BEAM INCORPORATED INTO THE UPPER COURSE. 107.2.1.3 |
| | DISCREPANCY IN PLANS, ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 4D) WITHIN THIS SUBMITTAL THERE ARE NO DETAILS OF HOW |
| | THE HISTORIC STRUCTURE IS GOING TO BE CUT LOOSE FROM |
| | ITS FOUNDATION NOR IS THERE ANY DETAILS OF HOW THE |
| | STRUCTURE IS TO BE LIFTED, IF THERE WILL BE ANY |
| | ADDITIONAL BEAMS OR LEDGERS FASTENED TO THE INTERIOR |
| | FRAMING TO BE ABLE TO LIFT THE BUILDING. THE MOVING |
| | CONTRACTOR HAS NOT SUBMITTED ANY DETAILS FOR THE MOVE, |
| | NOR HAS ANY SUCH DETAILS BEEN REVIEWED BY THE DESIGNER |
| | OF RECORD, SINCE THIS BUILDING IS A CONTRIBUTING |
| | HISTORIC STRUCTURE SUCH INFORMATION SHOULD BE SUBMITTED |
| | TO ENSURE THE SAFE TRANSPORT TO ITS NEW LOCATION. |
| | |
| | 2014 EXISTING BUILDING CODE 1301.2 CONFORMANCE. |
| | THE BUILDING SHALL BE SAFE FOR HUMAN OCCUPANCY AS |
| | DETERMINED BY THE FLORIDA FIRE PREVENTION CODE AND THE |
| | FLORIDA BUILDING CODE, BUILDING. ANY REPAIR, |
| | ALTERATION, OR CHANGE OF OCCUPANCY UNDERTAKEN WITHIN |
| | THE MOVED STRUCTURE SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THIS CODE APPLICABLE TO THE WORK BEING PERFORMED. |
| | ANY FIELD-FABRICATED ELEMENTS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 4E) 2014 EXISTING BUILDING CODE 1302.7 REQUIRED |
| | INSPECTION AND REPAIRS. THE CODE OFFICIAL SHALL BE |
| | AUTHORIZED TO INSPECT, OR TO REQUIRE APPROVED |
| | PROFESSIONALS TO INSPECT AT THE EXPENSE OF THE OWNER, |
| | THE VARIOUS STRUCTURAL PARTS OF A RELOCATED BUILDING TO |
| | VERIFY THAT STRUCTURAL COMPONENTS AND CONNECTIONS HAVE |
| | NOT SUSTAINED STRUCTURAL DAMAGE. ANY REPAIRS REQUIRED |
| | BY THE CODE OFFICIAL AS A RESULT OF SUCH INSPECTION |
| | SHALL BE MADE PRIOR TO THE FINAL APPROVAL. |
| | |
| | 5) SHEET S-1: |
| | 5A) SHEET S-1 VERSES SHEET A-1. THIS IS A QUESTION THAT |
| | ONLY IS BEING ASKED BECAUSE OF VISITS TO THE EXISTING |
| | BUILDING LOCATION. SHEET A-1 DOES SHOW A TOP OF WALL |
| | ELEVATION OF 10 FEET 4 INCHES OR THE TOP OF THE DOUBLE |
| | TOP PLATE OF THE WALL SYSTEM. SHEET S-1 SHOWS ONLY 2 |
| | COURSES OF BLOCK ABOVE THE FLOOR SLAB SYSTEM OR 1 FOOT |
| | 4 INCHES IN HEIGHT. IN THE SITE VISIT THERE WAS A |
| | HORIZONTAL CRACK APPROXIMATELY 4 FOOT ABOVE THE SLAB |
| | WHERE THE BLOCK STEM WALL STOPPED AND THE WOOD FRAME |
| | WALL BEGAN. THE QUESTION IS WILL THE CEILING AND |
| | EXTERIOR WALLS BE 1 FOOT 8 INCHES SHORTER IN HEIGHT OR |
| | SHOULD THE BLOCK STEM WALL BE CONTINUE TO A HIGHER |
| | HEIGHT TO MAINTAIN THE 10 FOOT 4 INCHES SHOWN ON THE |
| | PLANS? HOW CRITICAL IS THE DIFFERENCE IN HEIGHT? |
| | 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED; THERE |
| | MAY BE A DISCREPANCY IN THE PLANS. |
| | |
| | 5B) SHEET S-1 DETAIL # 1 SHOWS THE TOP OF SLAB EVEN |
| | WITH GRADE, HOW WILL THE JOINT CREATED BETWEEN THE |
| | CONCRETE FLOOR SLAB AND BOTTOM COURSE OF BLOCK BE DAMP |
| | PROOFED (1805.2.2) OR WATER PROOFED IN ACCORDANCE WITH |
| | 1805.3.3. |
| | FBC-B 1805.3.3 JOINTS AND PENETRATIONS. JOINTS IN WALLS |
| | AND FLOORS, JOINTS BETWEEN THE WALL AND FLOOR AND |
| | PENETRATIONS OF THE WALL AND FLOOR SHALL BE MADE |
| | WATER-TIGHT UTILIZING APPROVED METHODS AND MATERIALS. |
| | |
| | PLEASE NOTE THE FOUNDATION IS REQUIRED TO BE A MINIMUM |
| | OF 12 INCHES BELOW GRADE AS SHOWN, 2016 FBC-B |
| | 1809.4. |
| | |
| | EXISTING BUILDING CODE. 1302.2.1.1 HISTORIC BUILDINGS. |
| | FOUNDATIONS OF RELOCATED HISTORIC BUILDINGS AND |
| | STRUCTURES SHALL COMPLY WITH THE FLORIDA BUILDING CODE, |
| | BUILDING. RELOCATED HISTORIC BUILDINGS SHALL OTHERWISE |
| | BE CONSIDERED HISTORIC BUILDINGS FOR THE PURPOSE OF |
| | THIS CODE. RELOCATED HISTORIC BUILDINGS AND STRUCTURES |
| | SHALL BE SO SITED THAT EXTERIOR WALL AND OPENING |
| | REQUIREMENTS COMPLY WITH THE FLORIDA BUILDING CODE, |
| | BUILDING OR THE COMPLIANCE ALTERNATIVES OF THIS CODE. |
| | |
| | 5C) PLEASE PROVIDE DETAILS FOR HOW THE NEW WINDOWS ARE |
| | TO BE INSTALLED SINCE THIS IS A HISTORIC STRUCTURE SHOW |
| | DETAILS FOR WINDOWS, ARE THEY TO BE RECESSED IN THE |
| | OPENINGS WITH THE USE OF A WINDOW BUCK OR WILL THE |
| | STUCCO BE REMOVED AROUND THE WINDOWS AND FINNED WINDOWS |
| | BE INSTALLED AT THE FACE OF THE FRAME WALL, WILL THERE |
| | BE ANY WINDOW BANDS AROUND THE WINDOW AND DOOR |
| | OPENINGS? |
| | |
| | 6) SHEET A-1: |
| | 6A) SHOWS IN THE ELEVATIONS WITH NEW WINDOW AND DOORS, |
| | PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS. |
| | |
| | 6B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 6C) THE NEW WINDOW AND DOORS WILL NEED TO HAVE |
| | HISTORICS? APPROVAL BEFORE THE BUILDING DEPARTMENT WILL |
| | BE ABLE TO APPROVE THE PRODUCT APPROVALS. 2014 |
| | FBC-EXISTING BUILDING CODE 1203.1 HISTORIC PRESERVATION |
| | GOAL. |
| | |
| | 7) PLEASE NOTE THIS STRUCTURE DOES NOT INDICATE HAVING |
| | A RESTROOM WITHIN THE BUILDING. PLEASE NOTE THIS |
| | BUILDING IS UNDERGOING A CHANGE OF OCCUPANCY FROM |
| | STORAGE TO A BUSINESS OCCUPANCY. |
| | 2014 EXISTING BUILDING CODE. 1010.1 INCREASED DEMAND. |
| | WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART OF |
| | AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW |
| | OCCUPANCY IS SUBJECT TO INCREASED OR DIFFERENT PLUMBING |
| | FIXTURE REQUIREMENTS OR TO INCREASED WATER SUPPLY |
| | REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, PLUMBING, THE NEW OCCUPANCY SHALL COMPLY WITH THE |
| | INTENT OF THE RESPECTIVE FLORIDA BUILDING CODE, |
| | PLUMBING PROVISIONS. |
| | 2014 EXISTING BUILDING CODE 1301.2 CONFORMANCE. THE |
| | BUILDING SHALL BE SAFE FOR HUMAN OCCUPANCY AS |
| | DETERMINED BY THE FLORIDA FIRE PREVENTION CODE AND THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |