| 2016-06-10 18:23:54 | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC, 5TH EDITION (2014). |
| | |
| | ***NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. WITH |
| | PROVISO THE OWNER/BUILDER MAY SUBMIT THE REQUIRED |
| | INFORMATION AFTER THE PERMIT IS ISSUED AND BEFORE |
| | REQUIRED INSPECTION TO AVOID CONFLICTS OR DELAYS. |
| | REVISION FEES MAY APPLY. OWNER/BUILDER TO ADVICE IF THE |
| | PROVISO OPTION IS PREFERRED AT THIS TIME OR IF |
| | RE-SUBMITTING REQUIRED INFORMATION BEFORE ISSUING THE |
| | PERMIT. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | RESPONSE: |
| | A) ENERGY CALCULATIONS SUBMITED ARE MISSING THE |
| | INSPECTION CHECKLIST AS REQUIRED BY SEC. R405.4.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) ITEM #5 SPECIFIES THAT THIS IS NOT WORST CASE. |
| | CLARIFY WHY PAGE 2 OF 5 SPECIFIES AN ANGLE ROTATION OF |
| | 180 DEGREES. THE CALCULATIONS NEED TO BE DONE TO THE |
| | ACTUAL ORIENTATION OF THE BUILDING. REVISE THE WALLS, |
| | DOORS AND WINDOWS INFORMATION ON PAGE 3 OF 5. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | MULTIPLE ORIENTATIONS IS ONLY ALLOWED WHEN THERE IS THE |
| | CONSTRUCTION OF A BUILDING MODEL. |
| | |
| | C) PROVIDE DOCUMENTATION OF THE COMPONENT EFFICIENCIES |
| | USED FOR THE WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR |
| | SPECIFIED ON ITEM # 7 OF THE ENERGY CALCULATIONS AS |
| | REQUIRED BY SEC. R405.4.3 (2) FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | NOTE: THIS IS REQUIRED WHEN THE ENERGY CALCULATIONS ARE |
| | USING ANOTHER EFFICIENCY FACTOR OTHER THAN THE SOFTWARE |
| | DEFAULT FACTOR FOR GLAZING. |
| | |
| | D) ITEM #9(C) CALLS FOR ADJACENT WOOD FRAME WALLS. |
| | CLARIFY WHERE ARE THE WOOD FRAMED WALLS. PLANS DON'T |
| | SHOW ANY. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | E) COMPLETE ALL THE INFORMATION ON TOP OF FORM |
| | INCLUDING BUILDER NAME, PERMIT OFFICE, JURISDICTION |
| | NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 2- NEED TO SPECIFY ON PLANS CARBON MONOXIDE ALARMS |
| | WITHIN 10 FEET OF ALL BEDROOMS AS REQUIRED BY SEC. R315 |
| | OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | RESPONSE: CARBON MONOXIDE ALARMS WERE SPECIFIED FOR THE |
| | ADDITION ONLY. NEED TO SPECIFY ALARMS FOR ALL BEDROOMS, |
| | INCLUDING THE EXISTING ONES. |
| | |
| | ORIGINAL COMMENT: |
| | 3- EXISTING AND DEMOLITION PLAN ON SHEET 2 SHOWS |
| | EXISTING MEDIA ROOM. ACCORDING TO CITY RECORDS AND |
| | PROPERTY APPRAISER THIS ROOM IS AN UNFINISHED ENCLOSED |
| | PORCH NOT A LIVING SPACE. REVISE AS REQUIRED. THIS ROOM |
| | MAY BE CONVERTED TO A MEDIA ROOM AS SHOWN ON SHEET 4 |
| | BUT NEEDS TO SHOW COMPLIANCE WITH THE ENERGY |
| | CALCULATIONS (WALLS AND CEILING INSULATION) AND WITH |
| | THE ELECTRICAL REQUIREMENTS ( SEE ELECTRICAL REVIEW |
| | COMMENTS). SEC. 102.2 CITY AMENDMENTS. |
| | RESPONSE: INFORMATION ON PROPOSED NEW FLOOR PLAN ON |
| | SHEET #4 WAS REVISED. NOW IT READS "EXISTING ENCLOSED |
| | PORCH". CLARIFY IF THIS ROOM IS GOING TO BE A MEDIA |
| | ROOM OR ENCLOSED PORCH. |
| | SHEET #1 SAYS "EXISTING ENCLOSED PORCH CONVERTED TO NEW |
| | MEDIA ROOM". PLEASE COORDINATE ALL PLANS IN ORDER TO |
| | HAVE A PROPER PLAN REVIEW. |
| | |
| | ORIGINAL COMMENT: |
| | 4- ROOF SHEATHING SPECIFICATIONS SHOWN ON NAILING |
| | DETAIL ON SHEET #8, TYPICAL WALL SECTION ON SHEET #9 |
| | AND ROOF SHEATHING NOTES ON SHEET #10 DON'T MATCH |
| | SPECIFICATIONS SHOWN ON FASTENER SCHEDULE ON SHEET #5. |
| | REVISE AS REQUIRED TO MATCH. NOTE: SEC. R803.2.3.1 |
| | FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS MIN. |
| | RESPONSE: SPECIFICATIONS WERE NOT CHANGED ON TYPICAL |
| | WALL SECTION ON SHEET #9. |
| | |
| | NEW COMMENT: |
| | 5- TRUSS PACKAGE WAS SUBMITTED AT THIS TIME. THERE IS |
| | NO NEED TO SUBMITT TRUSS PACKAGE FOR REVIEW. TRUSS |
| | PACKAGE MAY BE GIVEN TO THE BUILDING INSPECTOR AT TIME |
| | OF FRAMING INSPECTION. THE FOLLOWING NEEDS TO BE |
| | ADDRESSED BY THE TRUSS ENGINEER: |
| | A) NEED ORIGINAL SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| | RECORDS. RUBBER STAMP IS NOT ALLOWED. |
| | B) THE COVER PAGE IS MISSING AL THE INFORMATION OF THE |
| | STRUCTURAL ENGINEER OF RECORD AS REQUIRED BY SEC. |
| | 61G15-31.003. |
| | C) ALL THE GENERAL STANDARD ENGINEERING PAGES NEED |
| | ENGINEER'S ORIGINAL SEAL, SIGNATURE, DATE. AS REQUIRED |
| | BY SEC. 61G15-23.003 AND CHAPTER 471 FLORIDA STATUTES. |
| | D) REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY |
| | THE ENGINEER OF RECORD. |
| | NOTE: REVISED TRUSS PACKAGE MAY BE SUBMITTED TO THE |
| | BUILDING INSPECTOR AT TIME OF FRAMING INSPECTION. NO |
| | NEED TO RESUBMIT NOW. |
| | |
| | |
| | ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWINGS. DON'T STAPLE OLD DRAWINGS TO NEW SET OF |
| | PLANS. SUBMIT OLD DRAWINGS FOR REFERENCE. |
| | |