| Plan Review Notes For Permit 16031217 |
| Permit Number |
16031217 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-04 05:39:50 | 1) A TIME SWITCH IS REQD. ON THE HEATER. 2014 | | | FBC-ENERGY SEC.R403.9.2 TIME SWITCHES. | | | TIME SWITCHES OR OTHER CONTROL METHOD THAT CAN | | | AUTOMATICALLY TURN OFF AND ON HEATERS AND PUMPS | | | ACCORDING TO A PRESET SCHEDULE SHALL BE INSTALLED ON | | | ALL HEATERS AND PUMPS. HEATERS, PUMPS AND MOTORS THAT | | | HAVE BUILT IN TIMERS SHALL BE DEEMED IN COMPLIANCE WITH | | | THIS REQUIREMENT. | | | | | | EXCEPTIONS: | | | | | | 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP | | | OPERATION. | | | | | | 2. WHERE PUMPS ARE REQUIRED TO OPERATE SOLAR- AND | | | WASTE-HEAT-RECOVERY POOL HEATING SYSTEMS. | | | | | | 3. WHERE PUMPS ARE POWERED EXCLUSIVELY FROM ON-SITE | | | RENEWABLE GENERATION. | | | | | | 2) A VAPOR RETARDANT POOL COVER IS REQD. PER 2014 | | | FBC-ENERGY SEC.R403.9.3. | | | 3) THE HEATER SHALL BE PROVIDED WITH A MEANS OF | | | RETAINING WATER IN THE HEATER WHEN THE PUMP IS NOT IN | | | OPERATION. | | | R4501.14.2 WATER RETENTION. | | | IF A HEATER IS NOT EQUIPPED OR DESIGNED FOR AN APPROVED | | | PERMANENT BYPASS OR ANTISIPHON DEVICE, AN APPROVED | | | PERMANENT BYPASS OR ANTISIPHON DEVICE SHALL BE | | | INSTALLED TO PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN THE PUMP IS NOT IN OPERATION. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|