2016-04-05 11:49:59PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS TO
 SHOW THAT THE EXISTING SEVICE IS ADEQUATE. FBCR -
 E3602.2 THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE CALCULATIONS IS REQUIRED TO BE ON
 THE SUBMITTALS. FBC 107.2.1
  
 2) THE POOL HEATING EQUIPMENT IS REQUIRED TO BE
 GROUNDED AND BONDED. FBCR - E4205.1, FBCR - E4204.2
  
 3) AN ELECTRICAL SUB-PERMIT IS REQUIRED TO INSTALL
 POWER TO THE POOL HEATER. FBC 105.1
  