| Plan Review Notes For Permit 16031217 |
| Permit Number |
16031217 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-05 11:49:59 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF ELECTRICAL LOAD CALCULATIONS TO | | | SHOW THAT THE EXISTING SEVICE IS ADEQUATE. FBCR - | | | E3602.2 THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE CALCULATIONS IS REQUIRED TO BE ON | | | THE SUBMITTALS. FBC 107.2.1 | | | | | | 2) THE POOL HEATING EQUIPMENT IS REQUIRED TO BE | | | GROUNDED AND BONDED. FBCR - E4205.1, FBCR - E4204.2 | | | | | | 3) AN ELECTRICAL SUB-PERMIT IS REQUIRED TO INSTALL | | | POWER TO THE POOL HEATER. FBC 105.1 | | | |
|