| Plan Review Notes For Permit 16031217 |
| Permit Number |
16031217 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-04-05 11:43:28 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE POOL HEATING EQUIPMENT IS REQUIRED TO RESIST | | | WINDLOADS. SUBMIT POOL HEATER TIE DOWN DETAILS. FBCR - | | | M1307.2 | | | | | | 2) PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. | | | THE POOL HEATER IS REQUIRED TO BE INSTALLED AT OR ABOVE | | | 7.5' BFE. FBCR 322.1.6 | | | | | | 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | |
|