Plan Review Notes
Plan Review Notes For Permit 16031217
Permit Number 16031217
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-05 11:43:28PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE POOL HEATING EQUIPMENT IS REQUIRED TO RESIST
 WINDLOADS. SUBMIT POOL HEATER TIE DOWN DETAILS. FBCR -
 M1307.2
  
 2) PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 THE POOL HEATER IS REQUIRED TO BE INSTALLED AT OR ABOVE
 7.5' BFE. FBCR 322.1.6
  
 3) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  