2016-03-26 08:34:071) CLEARLY SHOW THE DEVELOPED LENGTH AND THE BTU LOAD
 OF THE 2 PSI SYSTEM ON THE GAS DRAWING. THE TOP OF THE
 DRAWING IS CUT OFF AND THE INFORMATION IS NOT CLEAR.
 FBC 107.2.1.
 2) CLEARLY IDENTIFY/LABEL THE STEP DOWN REGULATORS ON
 THE GAS DRAWING.
 3) EXPLAIN WHAT THE LETTERS "A" & "B" ON THE GAS
 DRAWING ARE FOR.
 4) INDICATE THE PIPE MATERIAL FOR THE 2 PSI 3/4" LINE
 FROM THE PE PIPE TO THE FUTURE SKILLET & THE FUTURE
 OVEN.IS THIS ALSO PE PIPE?
  
  