| Plan Review Notes For Permit 16031153 |
| Permit Number |
16031153 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-31 16:08:05 | ELECTRICAL REVIEW COMMENTS | | | REVIEWED FOR COMPLIANCE WITH: | | | 5TH EDITION FBC 2014, NFPA 70 2011 (NEC) | | | | | | CORRECTIONS REQUIRED: | | | 1. ACCORDING TO THE MANUFACTURER?S INSTRUCTIONS THIS | | | SYSTEM REQUIRES THAT IT BE HARD WIRED AND TIED IN TO | | | THE POOL?S EQUIPOTENTIAL BONDING GRID. | | | 2. PROVIDE A WIRING DIAGRAM INDICATING PROPER OVER | | | CURRENT AND GFI PROTECTION AND SYSTEM BONDING. | | | 3. INDICATE WHETHER THIS WILL BE POWERED USING 120 OR | | | 240 VAC. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|