| Plan Review Notes For Permit 16031092 |
| Permit Number |
16031092 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-25 06:45:02 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. INSUFFICIENT INFORMATION PROVIDED FOR DESCRIPTION OF | | | INSTALLATION. FBC 107.3.5 | | | 2. CLARIFY AMOUNT OF TANK-LESS WATER HEATERS BEING | | | INSTALLED. APPLICATION SAYS 8, ONLY 5 SHOWN DRAWINGS | | | 3. PROVIDE CUT SHEETS FOR UNITS. ARE THE UNITS | | | INSTALLED OUTDOORS OR INDOOR, STATE LOCATION WITHIN | | | CONDO. FBC 107.3.5 | | | 4. LABEL PANEL BOARD LOCATION WITHIN CONDO FOR | | | REFERENCE. FBC 107.3.5 | | | 5. BRANCH CIRCUITS TO BE IDENTIFIED POWERING UNITS. NEC | | | 408.4 | | | 6. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|