| Plan Review Notes For Permit 16031054 |
| Permit Number |
16031054 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-29 12:59:25 | POOL BOX | | 2016-03-29 09:04:58 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PROVIDE A GENERAL NOTE TO COMPLY WITH PART 4 AND 5 | | | OF NEC ARTICLE 680 | | | 2. PLEASE PROVIDE SPECIFICATION SHEET FOR ALL LIGHTING | | | FIXTURES BEING USED IN FOUNTAIN. FBC 107.3.5 | | | 3. SHOW THE BONDING ARRANGEMENTS TO COMPLY WITH NEC | | | 680.53 SPA AND FOUNTAIN. | | | 4. PROVIDE GFCI PROTECTION FOR THE LIGHTING CIRCUITS TO | | | FOUNTAIN, SHOW ON PANEL BOARD SCHEDULE. | | | 5. PROVIDE A NOTE TO COMPLY WITH NEC 680.41- EM SWITCH | | | SHUTOFF FOR SPA. | | | 6. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD | | | YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|