Plan Review Notes
Plan Review Notes For Permit 16031036
Permit Number 16031036
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-29 13:01:06POOL BOX
2016-03-29 09:22:43INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE A GENERAL NOTE TO COMPLY WITH PART 2 OF NEC
 ARTICLE 680
 2. PLEASE PROVIDE SPECIFICATION SHEET FOR ALL
 ASSOCIATED POOL EQUIPMENT. FBC 107.3.5
 3. SHOW THE BONDING ARRANGEMENTS TO COMPLY WITH NEC
 680.26 FOR ALL.
 4. PROVIDE GFCI PROTECTION FOR POOL PUMPS, SHOW ON
 PANEL BOARD SCHEDULE PER NEC 680.21C
 5. PROVIDE A NOTE TO COMPLY WITH NEC 680.41- EM SWITCH
 SHUTOFF FOR SPA.
 6. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  