| 2016-04-06 13:11:51 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | | | | | | | - PROVIDE AN ELECTRICAL DETAIL DIAGRAM FOR THE SIGN | | | WITH THE FOLLOWING ITEMS. | | | | | | 1 NEC 600.6 20 AMP DEDICATED CIRCUIT | | | 2 NEC 600.6 DISCONNECT WITHIN SIGHT | | | 3 FBC-E C405.2.4 MUST BE ON A ASTRONAMICAL TIMER OR | | | COMBINATION PHOTOCELL / TIMER. |
|