| Plan Review Notes For Permit 16030910 |
| Permit Number |
16030910 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-25 16:03:16 | REVISION DENIED BY MECHANICAL | | | | | | 1) THE CFMS ARE NOT SPECIFIED FOR THE LIVING ROOM. FBC | | | 1007.2.1 | | | | | | 2) SEVERAL OF THE DUCT SIZES ARE NOT SPECIFIED ON THE | | | DRAWINGS. SPECIFY ALL DUCT SIZES. FBC 107.2.1 | | | | | | 3) IT APPEARS THAT ONE OF THE SUPPLY DUCTS TO THE | | | KITCHEN WAS MEANT TO BE DELETED. THERE ARE THREE | | | SUPPLIES SHOWN AT THE KITCHEN. PLEASE CLARIFY. FBC | | | 107.2.1 | | | | | | 4) THE WALL RETURN IS REQUIRED TO BE DUCTED. | | | FBCR-M1602.2 |
|