| Plan Review Notes For Permit 16030876 |
| Permit Number |
16030876 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-12 14:38:46 | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | PROVISO COMMENTS NOT REVISED ON RESUBMITTAL: | | | | | | 1. PROVISO AT AS-BUILT- ELECTRICAL SHEET- PLEASE | | | REFLECTS CURRENT BUILDING CODES. FLORIDA BUILDING CODE | | | 2014 5TH EDITION FAMILY, NEC 2011. | | | 2. SHOW THAT THERE IS A RECEPTACLE WITHIN 25FT TO | | | SERVICE UNIT. FBC RES E3901.12 | | | 3. SHOW THE SMOKE DETECTORS LAYOUT PER FBC RES 314 | | | REQUIREMENTS | | | 4. PROVIDE PER FBC RES E3609.3 INTERSYSTEM BONDING | | | TERMINAL | | | 5. PER PLAN ANNOTATIONS. FBC 107.3.5 | | | 6. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|