Plan Review Notes
Plan Review Notes For Permit 16030876
Permit Number 16030876
Review Stop B
Sequence Number 2
Notes
Date Text
2016-07-26 07:50:06RESIDENTIAL (R3) ALTERATIONS, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 ARCHITECT MAY BE CHARGE 4 TIMES THE PLAN REVIEW FEE AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B) IF PLANS
 CONTINUE TO BE DENIED.
  
  
 ORIGINAL COMMENT:
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION TO INCLUDE ALL THE
 ELECTRICAL, PLUMBING AND BUILDING WORK SHOWN ON PLANS
 AND ALL DESIGN PROFESSIONAL FEES. PLANS SHOW COMPLETE
 ALTERATION OF THE KITCHEN, INCLUDING THE RELOCATION OF
 THE KITCHEN SINK. NOTE: THERE IS A RED TAG ON THIS
 HOUSE FOR CONSTRUCTION WITHOUT PERMITS. INSPECTOR NOTED
 SHEATHING, LATH, DOORS WORK. THIS SCOPE OF WORK NEEDS
 TO BE ADDED TO THE VALUATION ALSO.
 RESPONSE:
 REPEAT COMMENT. VALUE DECLARED IN THE PERMIT
 APPLICATION DOESN'T REFLECT ALL THE ELECTRICAL,
 PLUMBING AND BUILDING WORK SHOWN ON PLANS. IT NEEDS TO
 INCLUDE THE DESIGN PROFESSIONAL FEES ALSO. UPDATE THE
 VALUE TO INCLUDE ALL LABOR, MATERIALS AND CONTRACTOR'S
 OVERHEAD AND PROFIT (EVEN IF IS DONE AS OWNER/BUILDER)
 AND INCLUDE DESIGN PROFESSIONAL FEES. PROVIDE COPY OF
 CONTRACT SIGNED WITH THE ARCHITECT FOR THE RENDERED
 SERVICES.
  
 ORIGINAL COMMENT:
 2- ARCHITECT TO PROVIDE COMPLETE DESIGN CRITERIA:
 SPECIFY CURRENT BUILDING CODE, BUILDING EXPOSURE,
 DESIGN PRESSURES FOR EXTERIOR DOORS AS REQUIRED BY SEC.
 R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE:
 EXTERIOR DOORS WERE REPLACED. SEE NOTE ON ITEM #1
 ABOVE.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- DETAIL SECTION SHOWN ON SHEET 2 OF 2:
 A) SPECIFY SIZE AND SPACING OF FRAMING MEMBERS TO SHOW
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) ARCHITECT TO CLARIFY WHY SPECIFYING "LSTA 18 EACH
 RAFTER". THIS IS A STRAP DESIGNED TO TRANSFER TENSION
 LOADS AND DOESN'T PROVIDE UPLIFT LOADS. ALSO, PROVIDE
 DETAIL SHOWING HOW THIS 18" LONG STRAP IS GOING TO BE
 INSTALLED IF THE STRAP IS NOT DESIGNED TO BE BENDED.
 PROVIDE CALCULATIONS SHOWING HOW THIS STRAP WILL RESIST
 THE UPLIFT LOADS OF SEC. R301 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C) ARCHITECT TO SPECIFY HOW THE RAFTERS ARE FASTENED TO
 THE EXISTING RAFTERS TO RESIST THE LOADS REQUIRED BY
 SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014). THERE
 IS A NOTE THAT READS "OVERLAP HEALTHY EXISTING RAFTERS
 MIN. 3'-0", SECURELY SPIKE TOGETHER". THIS IS NOT AN
 ACCEPTABLE SPECIFICATION. REVISE AS REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) PROVIDE COMPLETE INFORMATION FOR THE SOFFIT
 MATERIALS AND INSTALLATION SHOWING COMPLIANCE WITH SEC.
 R703.1.3 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 E) PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF
 SHEATHING. SPECIFY TYPE OF WOOD AND NAIL SIZE AND
 SPACING SHOWING COMPLIANCE WITH SEC. R803.2.3.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). NOTE: 8D RING
 SHANK NAILS ARE REQUIRED.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 EXTERIOR WALL AREAS THAT NEED TO BE REPAIRED AS NOTED
 ON ITEM #1 ABOVE WITH THE INSPECTOR RED TAG. SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) EXTERIOR DOORS A SHOWN ON PLANS AND NOTE ON ITEM #1
 ABOVE.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) ROOF SHINGLES FOR THE OVERHANG EXTENSION AS SHOWN ON
 PLANS
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 C) SIMPSON STRUCTURAL CONNECTOR SPECIFIED ON PLANS.
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE ARCHITECT'S SPECIFIED CONNECTOR OR
 ARCHITECT TO LIST THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED CONNECTOR.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
  
 NOTE: A SEPARATE ROOFING SUB-PERMIT WILL BE REQUIRED
 FOR THE SHINGLES INSTALLATION. ALSO, A SEPARATE PERMIT
 IS REQUIRED FOR A/C WORK.
  
 **** ARCHITECT TO PROVIDE RESPONSE LETTER ADDRESSING
 EACH STRUCTURAL COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved