2016-03-23 04:50:52APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO AT AS-BUILT- ELECTRICAL SHEET- PLEASE
 REFLECTS CURRENT BUILDING CODES. FLORIDA BUILDING CODE
 2014 5TH EDITION FAMILY, NEC 2011.
 2. SHOW THAT THERE IS A RECEPTACLE WITHIN 25FT TO
 SERVICE UNIT. FBC RES E3901.12
 3. SHOW THE SMOKE DETECTORS LAYOUT PER FBC RES 314
 REQUIREMENTS
 4. PROVIDE PER FBC RES E3609.3 INTERSYSTEM BONDING
 TERMINAL
 5. PER PLAN ANNOTATIONS. FBC 107.3.5
 6. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  