2016-05-18 16:52:102ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: IT APPEARS THAT COMMENTS FROM FIRST
 REVIEW WERE NOT ADDRESSED THIS IS THE SECOND REQUEST.
  
 1) SHT. LS.01 - THE OCCUPANCY OF THIS SPACE IS NOTED AS
 "MERCHANT" & "M" AND THE WORD "ASSEMBLY" IS HANDWRITTEN
 IN. ALSO, SHT. A.01 LISTS THE OCCUPANCY AS A-2.CLARIFY
 THE OCCUPANCY OF THIS SPACE PER 2014 FBC SEC.302.
 2) SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. IT
 APPEARS AS THOUGH THE OCCUPANT LOAD WILL EXCEED 50
 PERSONS.
 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC - ACCESSIBILITY SEC.
 609.4.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE UNDER
 THE SINK GREASE TRAP AND SUBMIT SIZING CALCULATIONS PER
 THE FPC SEC.1003.2, 1003.3.4.
 5) SHT. P.01 - AS DRAWN, THE URINAL IN THE MEN'S
 RESTROOM IS ON A WET VENT.ONLY THE FIXTURES IN A
 BATHROOM GROUP ARE PERMITTED ON A WET VENT PER THE 2014
 FPC SEC.912.1 ( REFER TO THE DEFINITION OF "BATHROOM
 GROUP" IN THE DEFINITIONS OF THE FPC.)
 6) SUBMIT AN EXPANDED SANITARY RISER FOR THE THREE
 COMPARTMENT SINK. IT IS EXTREMELY DIFFICULT TO REVIEW.
 FBC 107.2.1.
 7) THE WATER RISER SHOWS THE INSTALLATION OF AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED FOR THE CONTROL
 OF WATER HAMMER. WATER HAMMER ARRESTORS ARE REQUIRED
 AND SHALL COMPLY WITH 2014 FPC SEC.604.9.
 8) IS THIS A CHANGE OF OCCUPANCY? IF SO, THEN TWO
 DRINKING FOUNTAINS ARE REQUIRED PER THE FAC. SEC. 211.2
 AND FOOTNOTE # ( E ) OF TABLE 403.1 OF 2014 FPC.
  
 ADDITIONAL COMMENTS:
  
 9. URINAL SHALL COMPLY WITH FBC ACC SEC. 605.2 HEIGHT
 AND DEPTH.
 URINALS SHALL BE THE STALL-TYPE OR THE WALL-HUNG TYPE
 WITH THE RIM 17 INCHES (430 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. URINALS SHALL BE 13 1/2 INCHES
 (345 MM) DEEP MINIMUM MEASURED FROM THE OUTER FACE OF
 THE URINAL RIM TO THE BACK OF THE FIXTURE.
  
 605.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR FORWARD APPROACH SHALL BE PROVIDED.
  
 605.4 FLUSH CONTROLS.
 FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 SHOW DIMENSION ON PLAN PER WPB AMEND TO FBC 107.2.1
  
 10. DRINKING FOUNTAIN SHALL COMPLY WITH FBC ACC SEC.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 SHOW DIMENSIONS ON PLAN PER WPB AMEND TO FBC 107.2.1
  
 11. LAVATORY'S SHALL COMPLY WITH FBC ACC SEC. 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 SHOW DIMENSION ON PLAN PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  