| 2016-05-23 07:50:42 | 2ND REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16030858 |
| | 5/23/16 |
| | |
| | 1) THE RE-SUBMITTED MECHANICAL PLANS HAVE NOT BEEN |
| | REVISED OR CORRECTED COMPLETELY IN RESPONSE TO THE 1ST |
| | REVIEW COMMENTS, AND NO NARRATIVE RESPONSE WAS |
| | SUBMITTED TO EITHER REBUT THE COMMENTS OR CLARIFY THE |
| | SCOPE OF WORK. I AM RE-PRINTING THE COMMENTS BELOW FOR |
| | REVIEW: |
| | 1ST REVIEW COMMENT #1) THE PLANS APPEAR TO INDICATE A |
| | CHANGE USE OR OCCUPANCY AS DEFINED IN THE FBC-14 |
| | EXISTING BUILDING CODE. PLEASE REFER TO SECTION 1009.1 |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| | PROPOSED NEW BAR AND KITCHEN AREAS, AND ALL OTHER |
| | OCCUPIED ROOMS AND SPACES- SEE TABLE 403.3 FBC-14 |
| | MECHANCIAL AND PROVIDE A SCHEDULE THAT INCLUDES THE |
| | REQUIRED CFMS OF OUTDOOR AIR AND THE CFMS PROVIDED. |
| | PLEASE NOTE THE EXISTING AC SYSTEM(S) MAY HAVE TO BE |
| | ENLARGED TO PROVIDE ADEQUATE FRESH AIR AND CONDITIONING |
| | TO THE SPACE DUE TO THE INCREASED OCCUPANT LOAD- SUBMIT |
| | AC CALCULATIONS. |
| | 1ST REVIEW COMMENT #2) SHEET M0.1: PROVIDE A SCOPE OF |
| | WORK ON THE PLAN WITH CORRESPONDING DRAWINGS AND |
| | DETAILS INDICATING ALL ALTERATIONS TO THE EXISTING HVAC |
| | SYSTEMS. PLEASE NOTE THAT THE NEW KITCHEN WILL REQUIRE |
| | AN EXHAUST SYSTEM WITH A MINIMUM CAPACTITY OF .7 CFM |
| | PER SQ. FT. |
| | 1ST REVIEW COMMENT #3) PROVIDE AN EQUIPMENT SCHEDULE |
| | FOR THE NEW BATH EXHAUST FAN AND SHOW THE EXHAUST DUCT |
| | RUN AND TERMINATION LOCATION. |
| | 1ST REVIEW COMMENT #4) PLEASE NOTE THAT ADDITIONAL |
| | MECHANICAL COMMENTS MAY FOLLOW AFTER THE PLANS HAVE |
| | BEEN CORRECTED IN ACCORDANCE WITH ALL DEVELOPMENT |
| | DEPARTMENT REVIEWS. |
| | 2) PLEASE SHOW THE POINT OF CONNECTION FOR THE TWO |
| | TOILET ROOM EXHAUST DUCTS TO THE MAIN EXHAUST DUCT- THE |
| | CURRENT PLAN SHOWS ONE EXHAUST DUCT CONNECTING TWO |
| | FANS. PLEASE SEE TABLE 403.3 FOOTNOTE E AND INDICATE IF |
| | THE EXHAUST WILL RUN INTERMITTENLY OR CONTINUOUSLY WHEN |
| | OCCUPIED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |