Plan Review Notes
Plan Review Notes For Permit 16030858
Permit Number 16030858
Review Stop P
Sequence Number 1
Notes
Date Text
2016-04-18 06:32:551) SHT. LS.01 - THE OCCUPANCY OF THIS SPACE IS NOTED AS
 "MERCHANT" & "M" AND THE WORD "ASSEMBLY" IS HANDWRITTEN
 IN. ALSO, SHT. A.01 LISTS THE OCCUPANCY AS A-2.CLARIFY
 THE OCCCUPANCY OF THIS SPACE PER 2014 FBC SEC.302.
 2) SUBMIT THE CORRECT OCCUPANT LOAD FOR THE SPACE. IT
 APPEARS AS THOUGH THE OCCUPANT LOAD WILL EXCEED 50
 PERSONS.
 3) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER 2014 FBC - ACCESSIBILITY SEC.
 609.4.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE UNDER
 THE SINK GREASE TRAP AND SUBMIT SIZING CALCULATIONS PER
 THE FPC SEC.1003.2, 1003.3.4.
 5) SHT. P.01 - AS DRAWN, THE URINAL IN THE MEN'S
 RESTROOM IS ON A WET VENT.ONLY THE FIXTURES IN A
 BATHROOM GROUP ARE PERMITTED ON A WET VENT PER THE 2014
 FPC SEC.912.1 ( REFER TO THE DEFINITION OF "BATHROOM
 GROUP" IN THE DEFINITIONS OF THE FPC.)
 6) SUBMIT AN EXPANDED SANITARY RISER FOR THE THREE
 COMPARTMENT SINK. IT IS EXTREMELY DIFFICULT TO REVIEW.
 FBC 107.2.1.
 7) THE WATER RISER SHOWS THE INSTALLATION OF AIR
 CHAMBERS. AIR CHAMBERS ARE NOT APPROVED FOR THE CONTROL
 OF WATER HAMMER. WATER HAMMER ARRESTORS ARE REQUIRED
 AND SHALL COMPLY WITH 2014 FPC SEC.604.9.
 8) IS THIS A CHANGE OF OCCUPANCY? IF SO, THEN TWO
 DRINKING FOUNTAINS ARE REQUIRED PER THE FAC. SEC. 211.2
 AND FOOTNOTE # ( E ) OF TABLE 403.1 OF 2014 FPC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  