| 2016-03-25 12:29:07 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | | PERMIT 16030858 | | | 3/25/16 | | | | | | 1) THE PLANS APPEAR TO INDICATE A CHANGE USE OR | | | OCCUPANCY AS DEFINED IN THE FBC-14 EXISTING BUILDING | | | CODE. PLEASE REFER TO SECTION 1009.1 AND PROVIDE | | | MINIMUM VENTILATION CALCULATIONS FOR THE PROPOSED NEW | | | BAR AND KITCHEN AREAS, AND ALL OTHER OCCUPIED ROOMS AND | | | SPACES- SEE TABLE 403.3 FBC-14 MECHANCIAL AND PROVIDE A | | | SCHEDULE THAT INCLUDES THE REQUIRED CFMS OF OUTDOOR AIR | | | AND THE CFMS PROVIDED. PLEASE NOTE THE EXISTING AC | | | SYSTEM(S) MAY HAVE TO BE ENLARGED TO PROVIDE ADEQUATE | | | FRESH AIR AND CONDITIONING TO THE SPACE DUE TO THE | | | INCREASED OCCUPANT LOAD- SUBMIT AC CALCULATIONS. | | | 2) SHEET M0.1: PROVIDE A SCOPE OF WORK ON THE PLAN WITH | | | CORRESPONDING DRAWINGS AND DETAILS INDICATING ALL | | | ALTERATIONS TO THE EXISTING HVAC SYSTEMS. PLEASE NOTE | | | THAT THE NEW KITCHEN WILL REQUIRE AN EXHAUST SYSTEM | | | WITH A MINIMUM CAPACTITY OF .7 CFM PER SQ. FT. | | | 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW BATH | | | EXHAUST FAN AND SHOW THE EXHAUST DUCT RUN AND | | | TERMINATION LOCATION. | | | 4) PLEASE NOTE THAT ADDITIONAL MECHANICAL COMMENTS MAY | | | FOLLOW AFTER THE PLANS HAVE BEEN CORRECTED IN | | | ACCORDANCE WITH ALL DEVELOPMENT DEPARTMENT REVIEWS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|