| Date |
Text |
| 2016-03-24 11:03:35 | 255 EVERNIA STREET SUITE MU-4 |
| | PERMIT #16030858 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE |
| | PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| | (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| | FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |
| | SHEET LS-01: THE PLAN INDICATES A MERCANTILE OCCUPANCY |
| | UTILIZING AN OCCUPANCY LOAD FACTOR OF 30 SQ.FT. PER |
| | PERSON; HOWEVER, THIS OCCUPANCY IS AN ASSEMBLY |
| | OCCUPANCY REQUIRING AN OCCUPANT LOAD FACTOR OF 15 |
| | SQ.FT. PER PERSON. AN ASSEMBLY OCCUPANCY IS DEFINED IN |
| | THE FIRE CODE AS, "AN OCCUPANCY USED FOR A GATHERING OF |
| | 50 OR MORE PERSONS FOR DELIBERATION, WORSHIP, |
| | ENTERTAINMENT, EATING, DRINKING, AMUSEMENT, AWAITING |
| | TRANSPORTATION, OR SIMILAR USES." TWO EXITS EQUIPPED |
| | WITH PANIC HARDWARE WILL BE REQUIRED. THE COMMON PATH |
| | OF TRAVEL FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| | LOAD OF MORE THAN 50 PERSONS IS LIMITED TO 20 FEET. |
| | |
| | SUB-PERMITS: SEPARATE PLANS AND PERMITS ARE REQUIRED |
| | FOR THE INSTALLATION OR MODIFICATION OF THE FIRE |
| | SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |
| | |