Plan Review Notes
Plan Review Notes For Permit 16030858
Permit Number 16030858
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-24 06:57:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PROVISO ELECTRICAL SHEET- PLEASE REFLECTS CURRENT
 BUILDING CODES. FLORIDA BUILDING CODE 2014 5TH EDITION
 FAMILY, NEC 2011.
 2. PLEASE PROVIDE A NOTE PER NEC 210.8B (2)(5) GFCI
 PROTECTION AT BAR AREA AND FOOD PREPARATION AREAS
 REQUIRED.
 3. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
  
  
  