2016-05-26 08:54:182ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030836
 5/26/16
  
 1) THE REVISED PLAN INDICATES A NEW PLENUM SPACE ABOVE
 THE CEILING IN THE BACK ROOM AREAS- PLEASE PLACE NOTES
 ON THE PLANS PURSUANT TO SECTIONS 602 FBC-14
 MECHANICAL, AND SECTION C403.2.7.3 FBC-14 ENERGY
 CONSERVATION.
 2) SUBMIT UPDATED ENERGY CALCULATIONS- THE SUBMITTED
 FORM IS OUTDATED. THE CURRENT CODE IN EFFECT IS 2014-
 SEE SECTION C401.2 FBC-14 ENERGY CONSERVATION FOR
 COMPLIANCE PATHS. PLEASE NOTE THAT TWO COPIES OF ALL
 SUBMITTALS IS REQUIRED.
 3) INDICATE HOW ACCESS FOR SERVICE AND MAINTENANCE OF
 AHU-1 WILL BE PROVIDED- SECTION 306.1 FBC-14
 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER