| Plan Review Notes For Permit 16030836 |
| Permit Number |
16030836 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-05-26 08:54:18 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030836 | | | 5/26/16 | | | | | | 1) THE REVISED PLAN INDICATES A NEW PLENUM SPACE ABOVE | | | THE CEILING IN THE BACK ROOM AREAS- PLEASE PLACE NOTES | | | ON THE PLANS PURSUANT TO SECTIONS 602 FBC-14 | | | MECHANICAL, AND SECTION C403.2.7.3 FBC-14 ENERGY | | | CONSERVATION. | | | 2) SUBMIT UPDATED ENERGY CALCULATIONS- THE SUBMITTED | | | FORM IS OUTDATED. THE CURRENT CODE IN EFFECT IS 2014- | | | SEE SECTION C401.2 FBC-14 ENERGY CONSERVATION FOR | | | COMPLIANCE PATHS. PLEASE NOTE THAT TWO COPIES OF ALL | | | SUBMITTALS IS REQUIRED. | | | 3) INDICATE HOW ACCESS FOR SERVICE AND MAINTENANCE OF | | | AHU-1 WILL BE PROVIDED- SECTION 306.1 FBC-14 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|