| Plan Review Notes For Permit 16030836 |
| Permit Number |
16030836 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-25 11:26:50 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030836 | | | 3/25/16 | | | | | | 1) THE 24"X24" TRANSFER GRILL IS UNDERSIZED PER SECTION | | | 601.5 FBC-14 MECHANICAL. THE GRILL SHALL HAVE A MINIMUM | | | OF 1325 SQ. INCHES OF FREE AIR SPACE TO RETURN 2650 | | | CFMS OF SUPPLY AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|