| Plan Review Notes For Permit 16030836 |
| Permit Number |
16030836 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-21 18:19:29 | PASSED WITH A PROVISO | | | | | | | | | - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A | | | BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL | | | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION | | | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER | | | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING | | | POWER DENSITY CHART TO SHOW COMPLIANCE. ACCORDING TO | | | THE CHART 1.4 WATTS PER SQUARE FEET IS THE ALLOWANCE | | | FOR RETAIL THEREFORE YOUR DESIGN OF 3156 WATTS IS | | | NON-COMPLIANT. REEVALUATE AND ADJUST. | | | - SHOW WINDOWS SHALL BE CALCULATED AT 125 % FOR | | | CONTINUOUS LOAD DEMANDS , HOWEVER THIS DOESN?T | | | INFLUENCE THE LOAD CAPACITY BUT SINCE CALCULATION WERE | | | ITEMIZED IT WILL COMPROMISE THE INTEGRITY OF THE PRINT | | | RE-ADJUST ACCORDINGLY. NEC 220 AND DEFINITIONS ARTICLE | | | 100 ?CONTINUOUS LOAD?. | | | - NEC 110.16,110.24 PROVIDE ARC-FLASH HAZARD WARNING | | | LABEL AND AVAILABLE FAULT CURRENT MARKING. | | | | | | | | | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6713 | | | [email protected] | | | |
|