Plan Review Notes
Plan Review Notes For Permit 16030836
Permit Number 16030836
Review Stop E
Sequence Number 1
Notes
Date Text
2016-03-21 18:19:29PASSED WITH A PROVISO
  
  
 - FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE. ACCORDING TO
 THE CHART 1.4 WATTS PER SQUARE FEET IS THE ALLOWANCE
 FOR RETAIL THEREFORE YOUR DESIGN OF 3156 WATTS IS
 NON-COMPLIANT. REEVALUATE AND ADJUST.
 - SHOW WINDOWS SHALL BE CALCULATED AT 125 % FOR
 CONTINUOUS LOAD DEMANDS , HOWEVER THIS DOESN?T
 INFLUENCE THE LOAD CAPACITY BUT SINCE CALCULATION WERE
 ITEMIZED IT WILL COMPROMISE THE INTEGRITY OF THE PRINT
 RE-ADJUST ACCORDINGLY. NEC 220 AND DEFINITIONS ARTICLE
 100 ?CONTINUOUS LOAD?.
 - NEC 110.16,110.24 PROVIDE ARC-FLASH HAZARD WARNING
 LABEL AND AVAILABLE FAULT CURRENT MARKING.
  
  
 REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER