Plan Review Notes
Plan Review Notes For Permit 16030836
Permit Number 16030836
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-01 10:03:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16030836
 ADD: 701 S. ROSEMARY AVE. SUITE # 123
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-213-6975
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. APRIL 1/ 2016
 ACTION: DENIED
  
 1) SHEET A101:
 1A) THE THE COVERSHEET LIST THE OCCUPANT LOAD OF 54
 OCCUPANTS WITH THE REQUIRED 2 EXITS. THERE IS NO LIFE
 SAFETY PLANS SHOWING WHERE THE 2ND REQUIRED EXIT IS
 LOCATED. WITH THE 2ND EXIT BEING A BACK OF HOUSE EXIT
 DISCHRGE INTO A EXIT PASSAGEWAY. ASSUMED DOOR # 4 BEING
 THE EXIT FROM THE TENNANT SPACEINTO THE 1 HOUR FIRE
 RATED EXIT PASSAGE WAY THE WALLS OF THE BACK OF HOUSE
 EXIT PASSAGEWAY SHOULD SHOW AS A ONE HOUR FIRE RATING
 WITH OPENING PROTECTIVE RATING AT DOOR # 4 EVEN IF
 EXISITNG SHOW RATING.
  
 2014 FBC-B 1023.3 CONSTRUCTION. EXIT PASSAGEWAY
 ENCLOSURES SHALL HAVE WALLS, FLOORS AND CEILINGS OF NOT
 LESS THAN A 1-HOUR FIRE-RESISTANCE RATING, AND NOT LESS
 THAN THAT REQUIRED FOR ANY CONNECTING INTERIOR EXIT
 STAIRWAY OR RAMP. EXIT PASSAGEWAYS SHALL BE CONSTRUCTED
 AS FIRE BARRIERS IN ACCORDANCE WITH SECTION 707 .
  
 2014 FBC-B 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES.
  
 1B) NOTE ON THE PLAN INDICATING (E) EXISITING STEEL
 COLUMN WITH NEW SURROUND. 2 1/2 INCH STEEL STUDS WITH
 TYPE X 5/8 INCH GYPSUM BOARD TO DECK ABOVE. THE STEEL
 COLUMN AS SHOWN PENETRATES THE 1 HOUR FIRE RATED WALL.
 PLEASE NOT ONLY PROVIDE A UL NUMBER FOR WALL RATING BUT
 SHOW THE ACTUAL UL DETAIL ASSEMBLY FOR THE INSPECTOR
 WILL BE ABLE TO VIEW THE WALL CONSTRUCTION AS PER THE
 UL FIRE RATING.
 2014 FBC-B 708.4. CONTINUITY.
  
 1C) PLEASE SHOW COMPLIANCE WITH 2014 FBC-B 906.1 WHERE
 FIRE EXTINGUISHERS ARE REQUIRED.
  
 2) SHEET A102 THE REFLECTED CEILING PLAN (2) EXITS
 REQUIRED. THE PLANS SHOWS THE EXIT SIGN OVER THE FRONT
 ENTRY DOOR BUT NOT OVER THE DOORWAY LEADING TO THE BACK
 OF HOUSE AREA AND THE 2ND REQUIRED EXIT.
 2014 1015.1 TABLE 1015.1 SPACES WITH ONE EXIT OR EXIT
 ACCESS DOORWAY.
 2014 FBC-B SECTION 1011 EXIT SIGNS 1011.1 WHERE
 REQUIRED.
  
 3) SHEET A201 DETAILS 1 & 5 SHOW THE ACCESSIBLE
 HANDRAIL CENTERLINE 33-36 INCHES WHEREAS THE 2014
 FBC-ACCESS. CODE 609.4 POSITION OF GRAB BAR IS MEASURED
 FROM FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE
 NOT THE CENTERLINE.
  
 4) SHEET A300 INDICATES NEW STOREFRONT WINDOW UNITS AS
 WELL AS NEW STORFRONT DOORS. PLEASE SHOW COMPLIANCE
 WITH:
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. /MULLIONS
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS/ MULLIONS
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) FOR ALL PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE
 OPENING WIDTH & HEIGHT, TYPE OF GLAZING, MULLION
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7) 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  