Plan Review Notes
Plan Review Notes For Permit 16030772
Permit Number 16030772
Review Stop M
Sequence Number 1
Notes
Date Text
2016-03-21 12:13:571ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030772
 3/21/16
  
  
 1) SHEET M1: ALL CODE REQUIRED DUCT SMOKE DETECTORS
 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS, PLEASE
 REVISE NOTE #1 AND INDICATE IF ALL THE SYSTEMS WILL BE
 LINKED TOGETHER FOR FAN SHUT IF ANY SINGLE DETECTOR
 ACTIVATES.
 2) M1: THE 10" FLEX DUCTS SUPPLYING 350 CFMS FOR AHU'S
 #1, 2, & 6 NEED TO INCREASE TO 12".
 3) M1: THE EXHAUST FROM EF-1 SHALL DISCHARGE TO THE
 OUTDOORS IN ACCORDANCE WITH SECTION 501.3 FBC-14
 MECHANICAL.
 4) M2: THERE IS A DETAIL FOR TIE DOWN OF A AC CONDENSER
 UNIT TO AN EXISTING ROOF STAND, HOWEVER THERE ARE NO
 NEW CONDENSERS SHOWN ON THE PLANS: PLEASE CLARIFY
 5) PROVIDE NOTE AND DETAILS INDICATING HOW ACCESS FOR
 SERVICE AND REPLACEMENT OF THE ABOVE CEILING AHU'S AND
 MOTORIZED DAMPERS WILL BE PROVIDED.
 6) M2: PROVIDE HANGING, REINFORCEMENT, AND CONNECTION
 DETAILS FOR THE RIGID DUCTS IN ACCORDANCE WITH TABLE
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  