| Plan Review Notes For Permit 16030772 |
| Permit Number |
16030772 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-21 12:13:57 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030772 | | | 3/21/16 | | | | | | | | | 1) SHEET M1: ALL CODE REQUIRED DUCT SMOKE DETECTORS | | | SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS, PLEASE | | | REVISE NOTE #1 AND INDICATE IF ALL THE SYSTEMS WILL BE | | | LINKED TOGETHER FOR FAN SHUT IF ANY SINGLE DETECTOR | | | ACTIVATES. | | | 2) M1: THE 10" FLEX DUCTS SUPPLYING 350 CFMS FOR AHU'S | | | #1, 2, & 6 NEED TO INCREASE TO 12". | | | 3) M1: THE EXHAUST FROM EF-1 SHALL DISCHARGE TO THE | | | OUTDOORS IN ACCORDANCE WITH SECTION 501.3 FBC-14 | | | MECHANICAL. | | | 4) M2: THERE IS A DETAIL FOR TIE DOWN OF A AC CONDENSER | | | UNIT TO AN EXISTING ROOF STAND, HOWEVER THERE ARE NO | | | NEW CONDENSERS SHOWN ON THE PLANS: PLEASE CLARIFY | | | 5) PROVIDE NOTE AND DETAILS INDICATING HOW ACCESS FOR | | | SERVICE AND REPLACEMENT OF THE ABOVE CEILING AHU'S AND | | | MOTORIZED DAMPERS WILL BE PROVIDED. | | | 6) M2: PROVIDE HANGING, REINFORCEMENT, AND CONNECTION | | | DETAILS FOR THE RIGID DUCTS IN ACCORDANCE WITH TABLE | | | C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|