Plan Review Notes
Plan Review Notes For Permit 16030755
Permit Number 16030755
Review Stop B
Sequence Number 3
Notes
Date Text
2016-04-02 11:03:23RE-ROOF THIRD BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- RAS 117 CALCULATIONS SUBMITTED:
 A) THE NAIL ENHANCEMENT PATTERN SPECIFIED BY THE
 ENGINEER FOR ZONE 1 IS LESS THAN THE THE NAILING
 PATTERN SPECIFIED ON NEW ASSEMBLY W-62. THE NAILING
 PATTERN CAN NOT BE LESS THAN THE PATTERN SPECIFIED BY
 THE SELECTED ASSEMBLY. SEE SEC. 8.1 OF RAS 117. (REPEAT
 COMMENT).
  
 B) NAIL SPACING FOR ZONE #3 CAN NOT BE LESS THAN 4"
 O.C.. SEE RAS 117 SEC. 8.1.
  
 C) THE DESIGN PRESSURES SHOWN ON THE ACTUAL RAS 117
 CALCULATIONS SUBMITTED DON'T MATCH THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON THE COVER PAGE SUBMITTED.
 REVISE AS REQUIRED. SEC. 1609.1 OF FBC-BUILDING, 5TH
 EDITION (2014).
  
 D) THE BASE SHEET WIDTH SHOWN ON THE ACTUAL RAS 117
 CALCULATIONS IS INCORRECT. SEE GLASBASE BASE SHEET
 TECHNICAL INFORMATION AND REVISE AS REQUIRED. INCORRECT
 SIZE MAY AFFECT THE CALCULATIONS. SEC. 1609.1 OF
 FBC-BUILDING, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]