2016-03-23 08:26:58RE-ROOF SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 1- THE DESIGN PRESSURES OF SELECTED ASSEMBLY W-58 ARE
 -45PSF. THESE PRESSURES ARE LOWER THAN THE ENGINEER'S
 CALCULATED DESIGN PRESSURES SUBMITTED FOR ROOF ZONE #1.
 THE SELECTED ASSEMBLY CAN NOT BE USED. SEE NOTE #8 OF
 FLORIDA PRODUCT APPROVAL FL2533-R5 SUBMITTED AND SEC.
 8.1 OF RAS 117. REVISE AS REQUIRED TO COMPLY.
  
 RESPONSE:
 THE NAIL ENHANCEMENT PATTERN SPECIFIED BY THE ENGINEER
 IS LESS THAN THE THE NAILING PATTERN SPECIFIED ON NEW
 ASSEMBLY W-61. THE NAILING PATTERN CAN NOT BE LESS THAN
 THE PATTERN SPECIFIED BY THE SELECTED ASSEMBLY. SEE
 SEC. 8.1 OF RAS 117. ENGINEER TO PROVIDE COMPLETE RAS
 117 CALCULATIONS AS REQUIRED BY SEC. 107.2.1.3 CITY
 AMENDMENTS.
 NOTE: CALCULATIONS SUBMITTED REFER TO ASCE 7-05.
 ENGINEER TO PROVIDE CALCULATIONS USING ASCE 7-10 WHICH
 IS THE CURRENT EDITION ADOPTED BY FBC-2014.
  
  