| Plan Review Notes For Permit 16030755 |
| Permit Number |
16030755 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-18 11:00:04 | RE-ROOF BUILDING REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014) | | | | | | 1- THE DESIGN PRESSURES OF SELECTED ASSEMBLY W-58 ARE | | | -45PSF. THESE PRESSURES ARE LOWER THAN THE ENGINEER'S | | | CALCULATED DESIGN PRESSURES SUBMITTED FOR ROOF ZONE #1. | | | THE SELECTED ASSEMBLY CAN NOT BE USED. SEE NOTE #8 OF | | | FLORIDA PRODUCT APPROVAL FL2533-R5 SUBMITTED AND SEC. | | | 8.1 OF RAS 117. REVISE AS REQUIRED TO COMPLY. | | | | | | 2- ROOF ASSEMBLY COMPONENTS SPECIFIED BY THE ENGINEER | | | DON'T MATCH COMPONENTS SHOWN ON THE SELECTED APPROVED | | | ASSEMBLY W-58 SUBMITTED. ENGINEER TO MATCH | | | SPECIFICATIONS WITH SELECTED ASSEMBLY. ALSO, COORDINATE | | | WITH ITEM #1 ABOVE. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 3- | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|