2016-03-18 11:00:04RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- THE DESIGN PRESSURES OF SELECTED ASSEMBLY W-58 ARE
 -45PSF. THESE PRESSURES ARE LOWER THAN THE ENGINEER'S
 CALCULATED DESIGN PRESSURES SUBMITTED FOR ROOF ZONE #1.
 THE SELECTED ASSEMBLY CAN NOT BE USED. SEE NOTE #8 OF
 FLORIDA PRODUCT APPROVAL FL2533-R5 SUBMITTED AND SEC.
 8.1 OF RAS 117. REVISE AS REQUIRED TO COMPLY.
  
 2- ROOF ASSEMBLY COMPONENTS SPECIFIED BY THE ENGINEER
 DON'T MATCH COMPONENTS SHOWN ON THE SELECTED APPROVED
 ASSEMBLY W-58 SUBMITTED. ENGINEER TO MATCH
 SPECIFICATIONS WITH SELECTED ASSEMBLY. ALSO, COORDINATE
 WITH ITEM #1 ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 3-
  