Plan Review Notes
Plan Review Notes For Permit 16030728
Permit Number 16030728
Review Stop P
Sequence Number 2
Notes
Date Text
2016-04-14 16:33:37PLUMBING COMMENTS:
  
 1. SHT.P401 WATER RISER.
 (A) MISSING COLD WATER DROP FOR SHOWER 135
 (B) MISSING COLD WATER DROP FOR SHOWER 110
 (C) MISSING COLD WATER DROP FOR LAUNDRY SINK 121
 (D) AT BAR SINK THE HOT LOOP IS TIED TOGETHER AT THE
 MAIN , IT SHOULD BE SEPARATED IF YOUR TRYING TO CREATE
 CIRCULATED WATER TO BAR SINK.
 (E) THE FLOW DIRECTION ARROW ON HOT LOOP BETWEEN
 LAUNDRY SINK AND KITCHEN IS REVERSED.
 PLEASE CORRECT THESE OMISSIONS . PER WPB AMEND.TO FBC
 SEC.107.2.1
  
 2. SHT. P400 SANITARY RISERS.
 (A) SANITARY RISER S/3 SHALL BE SIZED. PER WPB AMEND.TO
 FBC SEC.107.2.1
 (B) SANITARY RISER S/9 THE WASHING MACHINE STAND PIPE
 IS NOT VENTED SHALL COMPLY WITH.
 FBC PL SEC.901.2 AND 901.2.1
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  