2016-04-14 07:39:042ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030728
 4/14/16
  
 1) SHEET D100 & M100: PLEASE REVISE THE PLAN SHEETS TO
 INCLUDE DETAILS FOR MECHANICAL DEMOLTION AND
 RE-CONSTRUCTION, AND PROVIDE A SCOPE OF WORK FOR THE
 PROJECT . IT APPEARS THAT DUE TO THE RE-CONFIGURATION
 OF THE UNIT LAYOUT, TWO EXISTING HEAT PUMPS ARE BEING
 REPLACED IN THE SAME LOCATIONS, AND TWO ADDITIONAL IN
 NEW LOCATIONS ARE BEING INSTALLED.
 2) PROVIDE AC LOAD CALCULATIONS FOR THE NEW HEAT PUMP
 SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION.
 3) PROVIDE A WATER PIPING LAYOUT PLAN AND PIPING
 INSTALLATION DETAILS.
  