| 2016-03-21 14:21:49 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16030728 | | | 3/21/16 | | | | | | 1) CLARIFY HOW OUTDOOR AIR IS BEING SUPPLIED TO THE | | | HEAT PUMPS- REFER TO SECTION 809.2 FBC-14 EXISTING | | | BUILDING AND PROVIDE CALCULATIONS IN ACCORDANCE WITH | | | TABLE 403.3 FBC-14 MECHANICAL. | | | 2) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION AND PROVIDE NON-COMBUSTIBLE DOORS FOR ALL | | | OF THE HP CLOSETS. | | | 3) PROVIDE THE SUPPLY CFM'S FOR THE 6X6 DIFFUSER IN THE | | | ELEVATOR HALL. | | | 4) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER | | | SECTION 603 FBC-14 MECHANICAL. | | | 5) A NEW CU IS SPECIFIED ON SHEET M301: INDICTE THE | | | LOCATION OF THE UNIT AND PROVIDE ENGINEERED | | | INSTALLATION DETAILS- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|