2016-03-21 14:21:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16030728
 3/21/16
  
 1) CLARIFY HOW OUTDOOR AIR IS BEING SUPPLIED TO THE
 HEAT PUMPS- REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING AND PROVIDE CALCULATIONS IN ACCORDANCE WITH
 TABLE 403.3 FBC-14 MECHANICAL.
 2) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND PROVIDE NON-COMBUSTIBLE DOORS FOR ALL
 OF THE HP CLOSETS.
 3) PROVIDE THE SUPPLY CFM'S FOR THE 6X6 DIFFUSER IN THE
 ELEVATOR HALL.
 4) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER
 SECTION 603 FBC-14 MECHANICAL.
 5) A NEW CU IS SPECIFIED ON SHEET M301: INDICTE THE
 LOCATION OF THE UNIT AND PROVIDE ENGINEERED
 INSTALLATION DETAILS- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  